SP3000 Non-Contact AC Voltage Probe
The SP3000 is a non-contact AC voltage waveform probe ideal for maintenance applications involving device control signals and sensor signals.
Simply apply the probe to a cable outside its insulation cover to capture the signal without exposing the technician to electrocution.
SP3000-01 | SP3000, SP9001 bundled model |
---|
Connect to a Memory HiCorder’s analog input terminal or oscilloscope. Both the SP3000 amplifier box and SP9001 probe head are necessary to measure. Select Model SP3000-01 for the entire system.
Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)[Head of probe] AC VOLTAGE PROBE SP9001
Measurement method | Capacitive-coupled current cancellation (not suitable for use with bare conductors) |
---|---|
Measurable wire type | Insulated wire |
Maximum input voltage | RMS : 30 Vrms or less, Peak : 42.4 Vpeak or less |
Dimensions and mass | 15.0 mm (0.59 in) W × 13.9 mm (0.55 in) H × 77.4 mm (3.05 in) D mm, 52 g (1.83 oz) (including cable) |
[Main body measuring circuit] NON-CONTACT AC VOLTAGE PROBE SP3000
Rated measurement voltage | 5 V rms (14.14 Vp-p) |
---|---|
Output rate | 1 V/V |
Rising time | 4.5 μs or less |
Frequency band | 10 Hz to 100 kHz (-3 dB) |
Voltage measurement precision | ±2.5% rdg. ±1% f.s. (0.5 Vrms to 5 Vrms) |
Effects of wire under measurement | ±5% rdg. (Finished outer diameter φ1.0 to 2.5 mm, in a wire rod in conformity with UL1007, UL1015, AV, AVS, AVSS) |
Power supply | (1)USB bus power: USB mini receptacle: 5 V ±0.25 V DC (2)AC Adapter Z1013: 5 V DC, 2.6 A Rated supply voltage: 100 V to 240 V AC (50 Hz/60 Hz) |
Output terminal | Insulated BNC (Measuring device connection side), Output resistance : 50 Ω |
Dimensions and mass | 120 mm (4.72 in) W × 25 mm (0.98 in) H × 55 mm (2.16 in) D, 160 g (5.64 oz) (including cable) |
Accessories | Ground connection cable (1.5 m) ×1, Alligator clip ×1, USB cable ×1, Instruction manual ×1 |