LRX Series One Line Single Phase Filters

LRX Series One Line Single Phase Filters

ETS-Lindgren’s One Line Single Phase Filters are individual, stand-alone single circuit filters from our LRX series of power line filters. ​​ETS-Lindgren manufactures UL Listed power line filters in a variety of mechanical configurations to meet your requirements. The basic, general purpose filter is the LRX series.

The One Line Single Phase Filters are available in two styles. The Style 2 (S2) type case configuration is designed for direct installation on a shielded room, whereas the Style 3 (S3) type case configuration is designed for installation within a shielded filter panel. Style 3 filters are often supplied as individual replacement filters for installation within the LPRX and LFPRX filter panels. The case configurations for Style 2 and Style 3 filters are shown below under Product Charts.

The LRX series of power line filters are designed for 277 volt line-to-ground, 480 volt line-to-line, 0 to 60 Hz applications. However, these filters can also be used for lower voltage ratings, such as 120/208 volts, with no adverse effect.

Model ​Stopband Insertion Loss ​Current Rating
​LRX-1010-S2

LRX-1010-S3

​​100 dB, 14 kHz to 40 GHz 10 A
​LRX-1030-S2

LRX-1030-S3

​​100 dB, 14 kHz to 40 GHz 30 A​
​LRX-1050-S2

LRX-1050-S3*

​​100 dB, 14 kHz to 40 GHz ​50 A​
​LRX-1060-S2

LRX-1060-S3

​​100 dB, 14 kHz to 40 GHz ​60 A​
​LRX-1100-S2

LRX-1100-S3

​​100 dB, 14 kHz to 40 GHz 100 A​
​LRX-1150-S2

LRX-1150-S3*

​​100 dB, 14 kHz to 40 GHz 150 A​
LRX-1200-S2

LRX-1200-S3

​​100 dB, 14 kHz to 40 GHz 200 A​
LRX-1225-S2

LRX-1225-S3*

​​100 dB, 14 kHz to 40 GHz 225 A​
​LRX-1250-S2

LRX-1250-S3

​​100 dB, 14 kHz to 40 GHz 250 A​
​LRX-1300-S21

LRX-1300-S21*

​100 dB, 14 kHz to 40 GHz ​300 A
​LRX-1400-S2

LRX-1400-S3

​100 dB, 14 kHz to 40 GHz ​400 A

NOTE: For Installation on shield, Style 2 (-S2) filters can be ordered with penetration kit. Add “/PEN” to model numbers.

Example: LRX-1100-S2/PEN.

1 Not UL Listed *Corresponding panel/cabinet is not UL listed.

 

Category:

Key Features

  • Part of Our LRX Series of Filters
  • Designed for 277 volt line-to-ground, 480 volt line-to-line, 0 to 60 Hz Applications
  • Manufactured to the most current version of UL-1283
  • In accordance with the Low Voltage Directive
  • LRX Power Line Filters meet the following standards:
  • MIL-F-15733
  • MIL-STD-220C
  • UL 1283 5th ed.
  • IEC 60939
  • LVD (2006/95/EC)

Application Notes