ETS-Lindgren’s Pulse Protected Powerline Filters with Red Edge Technology protects against damage to electronic equipment and loss of data caused by a sudden and intense electromagnetic pulse (EMP) and Intentional Electromagnetic Interference (IEMI). These filters provide excellent multi-stage, over-voltage, and EMI/ RFI protection. ETS-Lindgren is the only manufacturer to have their filters acceptance tested to the requirements of MIL-STD-188-125 by Little Mountain Test Facility operated by Boeing at Hill Air Force Base, in Ogden, Utah (test report available on request).
Model |
Amperage |
Short Circuit Current Rating (SCCR) |
Max Voltage |
Input Pulse Amplitude, E1, E2 |
Residual Requirement Amplitude and Filter Residual Let Through |
Typical Filter Response |
HEMP-2010 |
10 |
10 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-2030 |
30 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3030 |
30 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4030 |
30 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-2060 |
60 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3060 |
60 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4060 |
60 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-2100 |
100 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3100 |
100 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4100 |
100 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3250 |
250 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4250 |
250 |
25 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3X400 |
400 |
50 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4X400 |
400 |
50 k A |
277/480 |
2500 A; 250 A |
<10 A |
1No Filter Damage or Performance Degradation |
HEMP-3X600 |
600 |
125 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4X600 |
600 |
125 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3X800 |
800 |
125 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation n |
HEMP-4X800 |
800 |
125 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-3X1200 |
1200 |
150 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
HEMP-4X1200 |
1200 |
150 k A |
277/480 |
2500 A; 250 A |
<10 A |
No Filter Damage or Performance Degradation |
For other wire numbers or amperages please contact MDL Technologies.